| High-Voltage Rated Voltage | 6 kV–24 kV; up to 34.5 kV for North-American export | Low-Voltage Rated Voltage | 0.4 kV; export versions can be customized to 480 V / 208 V etc. |
|---|
| Rated Capacity | 50 kVA–2500 kVA | Frequency | 50 Hz; 60 Hz customizable for overseas projects |
|---|
| Power Supply Mode | Loop-feed type / Radial-feed type | Vector Group | Dyn11 / Yyn0 optional |
|---|
| Tap-Changer | Off-circuit tap changer ±2 × 2.5% | Cooling Type | ONAN – Oil Natural Air Natural cooling |
|---|
| Insulation Level | Matched with GB 1094 and ANSI C57 standards according to voltage class | Enclosure Protection | IP54 |
|---|
| Ambient Operating Temperature | -25 °C to +40 °C | High-Temperature Version | Up to +55 °C available |
|---|
| Transformer Structure | Fully-sealed, conservator-free oil-filled design | Installation | Outdoor pad-mounted installation |
|---|
| Overall Volume | Approx. 1/3 of a European-style box-type substation of equal rating | Low-Voltage Compartment | Independent air-insulated compartment |
|---|
| Core Material | High-permeability, low-loss grain-oriented silicon steel, M-4 / M-5 or equivalent | Core Construction | Five-step stepped-lap fully-mitered-joint construction |
|---|
| Tank Design | Fully-sealed tank without conservator | Tank Testing | Positive-pressure and negative-pressure tightness testing |
|---|
| Radiator Arrangement | External radiators with natural heat dissipation | Standard Anti-Corrosion | C3, C4, C5, CX-H |
|---|
| Heavy-Duty Anti-Corrosion | C5-M coating optional for coastal salt-spray environments | Dielectric Fluid | Mineral oil; high-fire-point eco-friendly dielectric fluid optional |
|---|
| High-Voltage Load Switch | 2-position / 4-position oil-immersed load switch | Fuse Protection | Bayonet-type fuse + backup current-limiting fuse |
|---|
| Surge Arrester | Oil-immersed surge arrester | High-Voltage Configuration | Fully integrated within the sealed transformer oil tank |
|---|
| Power Supply Configuration | Loop-feed / radial-feed | Cable Connection | Fully-insulated elbow-type cable connectors |
|---|
| Underground Cable Connection | Suitable for underground cable distribution systems | High-Voltage Component Testing | Oil-immersed voltage withstand and operation-cycle tests |
|---|
| Low-Voltage Compartment | Independent air-insulated compartment, fully separated from the oil-filled HV tank | Low-Voltage Equipment | Low-voltage circuit breakers, metering and outgoing circuits |
|---|
| Reactive Power Compensation | Optional | Intelligent Measurement & Control | Optional |
|---|
| Temperature Monitoring | PT100 temperature sensor optional | Oil-Level Monitoring | Oil-level indicator optional |
|---|
| Pressure Protection | Pressure-relief device optional | Remote Communication | Optional intelligent data acquisition and remote communication module |
|---|
| Communication Protocol | Modbus-RTU / Modbus-TCP | Monitoring Integration | Backend monitoring-platform connection supported |
|---|
| Noise Level | Typical ≤65 dB(A) at 1 m | Partial Discharge | <100 pC at 1.5 × rated voltage for transformer main body |
|---|
| Temperature Rise | Complies with GB 1094 and ANSI standards | Thermal Margin | ≥20% thermal margin reserved for short-time overload |
|---|
| Protection Performance | Two-stage dual-fuse protection for overload and short-circuit protection | Service Life | ≥30 years under normal outdoor operating conditions |
|---|
| Carbon Footprint Documentation | LCA life-cycle-assessment documentation available upon request | ESG Support | LCA documentation available to support customer ESG reporting |
|---|
| Typical Model | ZGS11-12/0.4-800 kVA loop-feed pad-mounted transformer | Primary Voltage | 10 kV |
|---|
| Secondary Voltage | 0.4 kV | Reference Cooling | ONAN – Oil Natural Air Natural cooling |
|---|
| Reference HV Configuration | 4-position oil-immersed load switch | Reference Protection | Bayonet-type fuse + backup fuse protection |
|---|
| LV Configuration | Low-voltage incoming + multiple outgoing circuits, metering and intelligent measurement-control unit | Reference Enclosure | IP54, C3, C4, C5, CX-H anti-corrosion coating |
|---|
| Reference Installation | Outdoor pad-mounted installation | Special Options | Elbow-type cable-connector interface and remote-communication module |
|---|
| North-American Standard | ANSI/IEEE C57.12.00 / C57.12.34 | Power Transformer Standard | IEC 60076 Series |
|---|
| Prefabricated Substation Standard | IEC 62271-202 | Chinese Prefabricated Substation Standard | GB/T 17467-2020 |
|---|
| Combined Transformer Standard | JB/T 10217 | Oil-Immersed Transformer Standard | GB 1094 Series |
|---|
| Low-Voltage Switchgear Standard | GB 7251 Series | Seismic Standard | IEEE 693 optional for high-seismic-zone projects |
|---|
| Export Substance Control | RoHS & REACH | PCB-Free Dielectric Fluid | EPA 40 CFR Part 761; mineral oil / high-fire-point ester fluid optional |
|---|