| High-voltage rated voltage | 6kV / 10kV / 35kV; customizable | Low-voltage rated voltage | Not applicable for this reactor configuration |
| Rated capacity | 50kvar – 60Mvar | Power Supply Mode | Series current limiting / filter / neutral earthing / motor starting / shunt compensation |
| Frequency | 50Hz; 60Hz customizable for overseas projects | Cooling Type | AN air natural cooling, dry type |
| Reactor Type | Dry-type iron-core reactor | Product Portfolio | Series current limiting reactor / filter reactor / neutral earthing reactor / motor starting reactor / shunt compensation reactor |
| Reactance Rate | 0.1% – 14% for series reactors; filter and neutral reactors customized | Insulation Level | Designed according to IEC 60076-6, GB/T 1094.6 and GB/T 25075 |
| Installation | Indoor / outdoor vertical mounting | Ambient Temperature | -40°C to +40°C |
| Environmental Adaptability | High-altitude, coastal salt-spray and extreme-cold versions available | Typical Model | 10kV, 2000kvar, 4.5% dry-type iron-core series reactor |
| Typical Rated Voltage | 10kV | Typical Rated Capacity | 2000kvar |
| Typical Reactance Rate | 4.5% | Typical Cooling Arrangement | AN air natural cooling |
| Anti-corrosion Grade | C3 standard; C5-M heavy anti-corrosion coating optional | Installation Environment | Indoor switchgear room or outdoor substation installation |
| Inductance Characteristic | Stable inductance within the rated operating range with segmented air-gap design | Saturation Control | Segmented air gaps suppress core saturation and reduce inductance degradation under harmonic loads |
| Partial Discharge Level | <=10pC at 1.1 x rated voltage | Noise Level | Typical 62dB(A) at 1m; low-noise version available |
| Short-circuit Withstand | Designed and validated according to IEC 60076-5 | Dynamic-force Safety Margin | >1.3 x calculated value |
| Thermal Performance | Temperature rise compliant with IEC / GB requirements | Harmonic Thermal Margin | Thermal margin reserved for harmonic-load operating conditions |
| Design Life | >=30 years under normal indoor / outdoor service conditions | Insulation Medium | Epoxy fiberglass dry encapsulation or varnish impregnation |
| Oil-free Design | Dry type, oil-free construction with no fire hazard from insulating oil | Carbon Footprint | LCA life-cycle assessment documentation available for ESG reporting |
| Core Material | High-permeability low-loss grain-oriented silicon steel | Core Air-gap Design | Segmented air-gap structure with high-temperature non-magnetic spacing blocks |
| Core Clamping | Robust clamping structure designed for mechanical stability | Core Coating | Insulating anti-corrosion paint |
| Conductor Material | Multi-strand parallel oxygen-free aluminum; copper optional | Conductor Insulation | Single-strand film insulation |
| Conductor Transposition | Transposition design to reduce harmonic eddy-current losses | Conductor Quality Control | Conductor material screened for resistivity consistency |
| Coil Encapsulation | Epoxy fiberglass or varnish impregnated construction | Coil Insulation | Sufficient turn and layer insulation redundancy with strict partial-discharge control |
| Support Insulators | High-strength epoxy insulators | Pollution Resistance | Hydrophobic and anti-pollution support structure |
| Metal Structure | Anti-corrosion coating with C3 standard protection | Coastal Protection | C5-M heavy anti-corrosion protection optional for coastal salt-spray environments |
| Auxiliary Accessories | Support insulators / earth terminals / corona shields / rain hoods | Temperature Monitoring | Optional fiber-optic temperature online monitoring system |
| Electromagnetic Design | 3D FEM electromagnetic analysis with air-gap and fringing-flux evaluation | Magnetic Field Analysis | Rated-load and harmonic-load loss calculation with inductance-current curve verification |
| Core Saturation Analysis | Local saturation control and inductance stability verification | Eddy-current Loss Analysis | Evaluation of core and winding eddy-current losses under rated and harmonic loads |
| Mechanical / Seismic Design | ANSYS structural analysis for short-circuit force, core clamping and support structures | Seismic Qualification | IEEE 693 seismic qualification available as an option |
| Short-circuit Simulation | Transient electromagnetic-field simulation for coil forces and structural stress | Mechanical Validation | Core clamp, support insulator and coil encapsulation strength verification |
| Insulation Coordination | Turn, layer and main insulation electric-field analysis | Impulse Withstand | Lightning impulse and switching impulse withstand verification |
| Thermal-flow Simulation | CFD analysis for steady-state and harmonic-load temperature rise | Hot-spot Control | Coil and core hot-spot temperature control under harmonic operation |
| Noise Optimization | Air-gap optimization and structural design to reduce vibration and noise | Stray-loss Optimization | Optimized magnetic-field distribution to reduce stray losses |
| Applicable Standards | IEC 60076-6 / GB/T 1094.6 / GB/T 25075 | North America Standard | IEEE C57.16 optional for export projects |
| Seismic Standard | IEEE 693 optional for high-seismic substations | Environmental Compliance | RoHS and REACH hazardous-substance control |
| Material Compliance | Key materials comply with IEC / GB requirements | Material Traceability | Full material traceability available |
| Factory Acceptance Test | Routine and type tests including inductance, DC resistance, loss, partial discharge and dielectric withstand | Witness Testing | Client or third-party witnessed testing available |
| Short-circuit Test | Short-circuit testing performed only by specialized authorized third-party laboratories | Factory Test Capability | Factory does not perform the specialized short-circuit test |
| Installation Support | Installation guidance, lifting supervision and pre-commissioning inspection | Commissioning Support | Commissioning assistance and technical support available |
| Warranty | Comprehensive product warranty | Extended Service | Extended service agreement optional |
| Spare Parts Supply | Minimum 25-year supply support for key components | Training | On-site or remote operation and maintenance training |
| Training Scope | Saturation, vibration, heating, operation and maintenance | Quality Management | ISO 9001 / ISO 14001 / ISO 45001 |
| Customization | Series / filter / motor-starting / neutral earthing / shunt compensation reactor configurations | Special Environment | High altitude, coastal salt spray, extreme cold and low-noise versions available |
| Typical Applications | PV / wind collection substations, power-grid substations and renewable-energy stations | Industrial Applications | Metallurgy, arc furnaces, VFD systems, cement and chemical plants |
| Power Grid Application | 10kV / 35kV series current-limiting reactors | Harmonic Mitigation | Filter iron-core reactors for industrial harmonic control |
| Motor Application | Motor starting reactors for generator and high-voltage motor circuits | Neutral Earthing Application | Neutral earthing reactors for high-voltage electrical systems |
| Reactive Compensation | Reactive compensation and harmonic-control applications | New-energy Application | PV / wind collection substations and renewable-energy power stations |
| Export Frequency | 60Hz versions customizable for overseas EPC projects | Design Workflow | Fully digital multi-physics simulation before manufacturing |
| Simulation Domains | Electromagnetic / thermal / fluid / structural / seismic | Performance Documentation | Traceable simulation and technical performance documentation available |