| Basic Electrical Parameters | |||
| High-voltage rated voltage | 6 kV, 10 kV, 20 kV, 35 kV (typical); custom voltages available | Rated capacity | Ground Mounted Transformer: Sized According To System Capacitive Current; Earthing-cum-station-service Transformer: 50 kVA – 2500 kVA |
| Power Supply Mode | Grounding And Station-service Power Supply; Suitable For Distribution Network And Substation Applications | Frequency | 50 Hz; 60 Hz Custom For Overseas Projects |
| Cooling Type | Oil-immersed: ONAN / ONAF; Dry-type: AN / AF; User-selectable | Fluid Type | Mineral Oil; Biodegradable Ester Fluids Optional |
| Winding Connection Vector Group | Znyn0 (Earthing-cum-station-service); Zn0 (Ground Mounted Transformer) | Zero-Sequence Impedance | Custom-designed According To System Capacitive Current And Arc-suppression Coil Parameters |
| Short-Time Earth-Fault Current | Custom Per Project System Parameters; Duration Options: 10 s / 60 s | No-Load Current | < 0.3% – 0.6% (Measured At Rated Voltage) |
| Tap-Changer | Off-circuit Tap-changer; On-load Tap-changer Generally Not Applied | Insulation Level | Matched To GB 1094 And IEC 60076-3 Per Voltage Class |
| Functional Type | Ground Mounted Transformer / Earthing-cum-station-service Transformer | Construction Type | Oil-immersed Type / Dry-type |
| Primary Voltage | 10 kV (Reference Application) | Secondary Station-Service Voltage | 0.4 kV (Reference Application) |
| Typical Model | 10 kV Znyn0 800 kVA Oil-immersed Earthing-cum-station-service Transformer | Reference Cooling Arrangement | ONAN Oil Natural-air Natural Cooling |
| Winding And Earthing Performance | |||
| Winding Connection Vector Group | Znyn0 (earthing-cum-station-service); Zn0 (Ground Mounted Transformer) | Zero-Sequence Impedance | Custom-designed according to system capacitive current and arc-suppression coil parameters |
| Short-Time Earth-Fault Current | Custom per project system parameters; duration options: 10 s / 60 s | Short-Time Earth-Fault Withstand | Complies with standard requirements for short-time single-phase earth-fault energization; winding temperature rise and mechanical strength satisfy GB 1094-5 |
| Winding Configuration | Z-type zig-zag winding; each phase consists of two half-windings connected in reverse series | Secondary Winding | Optional auxiliary secondary winding for station-service power supply |
| Zero-Sequence PT Interface | Available as a special option | Excitation Characteristics | Low excitation current; excitation curve keeps away from saturation zone to prevent ferro-resonance |
| No-Load Current | < 0.3% – 0.6% (measured at rated voltage) | Tap-Changer | Off-circuit tap-changer; on-load tap-changer generally not applied |
| Insulation And Dielectric Performance | |||
| Insulation Level | Matched to GB 1094 and IEC 60076-3 per voltage class | Partial Discharge Level | Oil-immersed: < 100 pC at 1.5 x rated voltage; dry-type meets GB 1094.11 partial discharge requirements |
| Dry-Type Insulation | F/H-class epoxy casting available | Dielectric Fluid | Mineral oil / biodegradable ester fluids optional |
| Thermal Performance | Long-term no-load temperature rise within standard limits; short-time fault heating under single-phase earth conditions calculated with safety margin | Service Life | >= 30 years under normal distribution network conditions |
| Core Material | High-permeability, low-loss grain-oriented silicon steel; M-4 / M-5 grade or equivalent | Noise Level | Typical <= 65 dB(A) at 1 m; low-noise version available upon request |
| Mechanical Construction And Protection | |||
| Functional Type | Ground Mounted Transformer / Earthing-cum-station-service transformer | Construction Type | Oil-immersed type / dry-type |
| Tank Sealing | Oil-immersed tank passes full vacuum and positive-pressure integrity tests | Dry-Type Enclosure | IP-rated protective enclosure optional |
| Corrosion Protection | C5-M high-corrosion-protection coating optional for coastal and chemically aggressive environments | Temperature Monitoring | PT100 winding-temperature sensors available for dry-type units |
| Special Configurations | Zero-sequence PT interface, temperature controller, oil-level monitoring available | Reference Cooling Arrangement | ONAN oil natural-air natural cooling |
| Reference Configuration And Compliance | |||
| Typical Model | 10 kV Znyn0 800 kVA oil-immersed earthing-cum-station-service transformer | Primary Voltage | 10 kV (reference application) |
| Secondary Station-Service Voltage | 0.4 kV (reference application) | Reference Cooling Arrangement | ONAN oil natural-air natural cooling |
| Standards | IEC 60076-1/2/3/5; IEC 61869; GB 1094.1-2-3-5; GB 1094.11; GB/T 10229-2019; DL/T 620; DL/T 1057; JB/T 10431 | Export Compliance | RoHS & REACH; EPA 40 CFR Part 761 PCB-free dielectric-fluid policy |
| Carbon Footprint | LCA life-cycle assessment documentation available upon request | Application | Ground-mounted grounding and station-service applications |