| Basic Electrical Parameters | |||
| Container dimension | 20ft / 40ft HC ISO standard; multi-module combined custom size available | High-voltage rated voltage | 6 kV – 35 kV (typical); custom higher voltage available |
| Low-voltage rated voltage | 0.4 kV, 6.6 kV, 10.5 kV, etc., customizable | Rated capacity | 500 kVA – 30 MVA; multi-module parallel for larger capacity |
| Power Supply Mode | Container Power Transformer System; Grid Connection And Renewable Energy Applications | Frequency | 50 Hz / 60 Hz, dual-frequency custom for overseas projects |
| Cooling Type | Transformer: ONAN / ONAF / OFAF; Container enclosure: air-conditioning + forced ventilation | Fluid Type | Mineral Oil; Ester Fluid Optional |
| Transformer Type | Oil-immersed Or Dry-type Transformer Optional | Typical Model | 40ft-HC Container-mounted Boost Power Station; 10 MVA, 35 kV / 0.69 kV |
| Primary voltage | 35 kV | Secondary voltage | 0.69 kV |
| Rated voltage class | According To Project Voltage Requirement | Application Type | Utility Grid Connection; Renewable Energy Power Conversion System |
| Protection And Control System | |||
| MV switchgear | SF6-insulated or air-insulated; IEC 62271 compliant; Remote control and SCADA communication supported | LV distribution | IEC 61439 compliant; ACB / MCCB, protection relays and metering devices |
| Control and protection | Integrated protection relay, data-acquisition unit and edge gateway | Remote monitoring | Remote monitoring, fault alarm and remote upgrade supported |
| Communication protocol | IEC 61850; Modbus-TCP/RTU; IEC 60870-5-104 | Special function | Remote monitoring; fault alarm; grid-code compliant voltage-reactive-power control |
| Fire-safety system | Multi-zone smoke-temperature composite detection; gas fire suppression; pressure-relief vents; emergency stop | Auxiliary power | UPS; ATS automatic transfer switch; auxiliary transformer; internal lighting and emergency stop device |
| Protection relay | Integrated digital protection system; Overcurrent, overload and fault protection functions | Metering system | Energy metering; Voltage, current and power monitoring |
| SCADA integration | SCADA communication interface available; Remote operation supported | Fault alarm | Local And Remote Fault Alarm Function |
| Container Structure And Environmental Conditions | |||
| Enclosure protection | IP54 standard; IP55 optional | Container protection | IP54; C5-M anti-corrosion coating |
| Operating ambient temperature | -25 °C ~ +55 °C High-low-temperature adaptation customized | Seismic requirement | Comply with IEEE 693 upon project request |
| Anti-corrosion coating | C3, C4, C5, CX-H | Mechanical impact resistance | IK10 for external surfaces |
| HVAC system | Air-conditioning + forced ventilation; Dehumidification and temperature/humidity monitoring available | Cooling arrangement | Transformer ONAF; Container air-conditioning + forced ventilation |
| Earthing system | Equipotential earthing grid inside container; Full-range lightning and surge protection | Noise emission | Typical ≤70 dB(A) at 1 m under full-load; Low-noise version available upon request |
| Service life | ≥25 years design service life under normal operating conditions | Environmental adaptability | Suitable for outdoor installation and harsh environmental conditions |
| Container material | High-strength steel structure; Outdoor weather-resistant design | Installation environment | Outdoor power generation and distribution applications |
| Transformer Technical Design | |||
| Transformer type | Oil-immersed transformer or dry-type transformer optional | Cooling arrangement | Transformer ONAF; Container air-conditioning + forced ventilation |
| Insulation system | Oil insulation system or dry-type insulation system according to transformer type | Transformer efficiency | High efficiency transformer design; Low-loss operation available |
| Transformer connection | According to grid connection requirements and project specifications | Voltage regulation | Designed according to system voltage regulation requirements |
| Short circuit withstand | Designed to withstand electrical and mechanical stress during short circuit conditions | Protection level | Integrated electrical and mechanical protection system |
| Installation And Standards | |||
| Deployment | 20ft / 40ft single-module or multi-module combined solution; Parallel expansion supported | Installation type | Factory assembled containerized installation; Outdoor installation available |
| Applicable standards | IEC 60076; IEC 62271-202; IEC 62271-1; IEC 61439; IEC 60529; IEC 62262 | Export compliance | RoHS and REACH; EPA 40 CFR Part 761 PCB-free dielectric-fluid requirement |
| Custom options | Custom voltage level; Capacity expansion; Protection configuration; Communication system customization | Project customization | Customized according to utility requirements, renewable energy projects and industrial applications |