| High-voltage rated voltage | 6kV / 10kV / 35kV / 66kV / 110kV; customizable | Low-voltage rated voltage | Not applicable |
| Rated capacity | 50kvar ~ 120Mvar | Power Supply Mode | Series / shunt / filter / neutral earthing / motor starting reactor |
| Frequency | 50Hz; 60Hz customizable for overseas projects | Cooling Type | AN air natural cooling, dry type |
| Product Type | Dry-type air-core reactor | Reactance Rate | Series reactor: 0.1% ~ 18%; shunt reactor customized on request |
| Insulation Level | Compliant with IEC 60076-6 and GB/T 1094.6 | Installation | Indoor / outdoor; vertical stacking or horizontal layout |
| Ambient Conditions | -40°C ~ +40°C; high altitude, coastal salt spray and extreme cold versions available | Insulation Medium | Epoxy glass fibre dry encapsulation; oil-free |
| Inductance Characteristic | No iron core saturation; high inductance linearity; stable inductance under harmonic conditions | Partial Discharge | <= 10pC at 1.1 x rated voltage |
| Noise Level | Typical 62dB(A) at 1m; low-noise version available | Short-Circuit Withstand | Designed and validated per IEC 60076-5 with dynamic force margin > 1.3 x calculated values |
| Thermal Performance | Temperature rise complies with IEC/GB standards; sufficient thermal margin under harmonic load | Design Life | >= 30 years under normal indoor / outdoor operating conditions |
| Conductor Material | Multi-strand parallel oxygen-free aluminium; copper optional | Conductor Insulation | Film insulation on individual strands with conductor transposition |
| Encapsulation System | Glass fibre + epoxy resin vacuum impregnated encapsulation; integral curing | Insulation Structure | Multi-layer encapsulation with turn-to-turn and layer insulation redundancy |
| Support Insulators | High-strength epoxy insulators; hydrophobic and anti-pollution | Anti-Corrosion Grade | C3, C4, C5, CX-H |
| Standard Accessories | Support insulators, earth terminals, corona shields and rain hoods | Temperature Monitoring | Fibre-optic temperature online monitoring optional |
| Design Method | Electromagnetic-thermal-flow-structural multi-physics coupled design | Electromagnetic Simulation | 3D FEM; inductance linearity; harmonic loss; turn-to-turn electric field; external magnetic field |
| Mechanical Simulation | ANSYS structural simulation; short-circuit electrodynamic force; encapsulation and support strength | Thermal-Flow Simulation | CFD natural convection simulation; steady-state and harmonic temperature rise prediction |
| Insulation Coordination | Turn-to-turn and layer insulation electric field simulation; lightning and switching impulse verification | Seismic Qualification | IEEE 693 compliance available as an option |
| Typical Model | 35kV, 12000kvar, 6% dry-type air-core series reactor | Reference Cooling | AN air natural cooling |
| Reference Installation | Outdoor substation installation | Reference Anti-Corrosion | C3, C4, C5, CX-H |
| Applicable Standards | IEC 60076-6; GB/T 1094.6; GB/T 25076 | Export Standards | IEEE C57.16 optional; IEEE 693 optional; RoHS and REACH |
| Quality System | ISO 9001; ISO 14001; ISO 45001 | Material Traceability | Key materials compliant with IEC/GB requirements with full traceability |
| Typical Applications | PV/wind power collection substations; power grid substations; rail transit; industrial VFD; arc furnace systems | Application Functions | Reactive power compensation; harmonic filtering; current limiting; neutral earthing; series resonance |
| Factory Acceptance Testing | Inductance measurement; resistance; loss; partial discharge; dielectric withstand tests | Third-Party Testing | Short-circuit testing by professional authorized third-party laboratories |
| Site Support | Installation guidance; lifting supervision; pre-commissioning inspection; commissioning support | Warranty | Comprehensive product warranty; extended service agreement optional |
| Spare Parts Supply | Minimum 25-year spare-parts supply for key components | Technical Training | On-site or remote O&M training covering magnetic field, heating and maintenance |
| Customization | Series / shunt / filter / neutral earthing reactors; adjustable reactance rate | Environmental Options | High altitude; coastal salt spray; extreme cold; low-noise versions |
| ESG Documentation | LCA life-cycle assessment documentation available upon request | Technical Documentation | Simulation reports; type-test reports; material certificates; material traceability documents |